A refrigerator uses refrigerant-134a as the working fluid and operates on the vapor-compression refrigeration cycle. The evap
A refrigerator uses refrigerant-134a as the working fluid and operates on the vapor-compression refrigeration cycle. The evaporator and condenser pressures are and , respectively. The isentropic efficiency of the compressor is 88 percent. The refrigerant enters the compressor at a rate of superheated by and leaves the condenser subcooled by . Determine the rate of heat removal from the refrigerated space, the rate of heat rejection from the refrigerant to the environment, the power input, and the COP if the cycle is operated on the ideal vapor-compression refrigeration cycle between the same pressure imits. (Take the required values from saturated refrigerant-134a tables.) The rate of heat removal from the refrigerated space is . The rate of heat rejection from the refrigerant to the environment is . The power input is . The COP is


We have an Answer from Expert

View Expert Answer

Expert Answer



We are given the following data:
Refrigerant: R-134a
Working fluid: Vapor-compression refrigeration cycle
Evaporator pressure: 180 kPa
Condenser pressure: 1400 kPa
Isentropic efficiency of compressor: 88%
Refrigerant mass flow rate: 0.021 kg/s
Superheating of refrigerant at compressor inlet: 12.73 °C
Subcooling of refrigerant at condenser outlet: 4.4 °C

Note :- I have used hin = h?