(Solved): 7. A reinforced concrete column 300mm in diameter is designed to carry an axial compressive load, ...
7. A reinforced concrete column 300mm in diameter is designed to carry an axial compressive load, P=1000kN as shown in Figure Q 7(a). Figure Q7 (b) shows the cross-section of the column at section a?a. Determine the required diameter of each reinforcing steel if the allowable stresses are 10MPa and 120MPa for the concrete and steel, respectively Use Ecamcrete ?=20GPa and Eseed ?=200GPa. [Ans: dsted ?=28.8mm ]